Product Code: 2389
The KEP AMP-1 signal conditioner amplifies the low level signals from a magnetic pickup or flow transmitter by a factor of more than a hundred times
to drive any ratemeter, counter or controller. The unit uses only 30 mA and operates from 11 to 26 VDC. It has a 2.7K pullup resistor
attached to the open collector output and sinks a minimum of 100 mA to less than 1 V from a maximum of 26 VDC. It is mounted
in a rugged 2″ x 3″ metal housing with screw terminals for easy installation. Operating temperature is 32 to 140°F (0 to 60°C). Note: The low voltage line from the magnetic pickup to the AMP-1 should be less than 10 ft. in length, shielded and isolated from
relays, solenoids or other sources of electrical noise (let the output line make the long run). If the input is too sensitive, lower the 1.1K
input impedance by adding a 220 to 1K ohm resistor across TB1, pins 1 and 2, to increase noise immunity. A special version, the AMP1-10k, is available with 10 kΩ impedance for use with turbine and paddle wheel flowmeters.
Mensor CPC4000 Pressure Controller
Flomec GPI G2 Turbine Flow Meter with Q9 Display
Rosemount 1066 Single Channel Transmitter
Eaton FHF Weatherproof ResistTel Hazardous Area Telephone
Panametrics PanaFlow MV84 Vortex Flow Meter
Rosemount 2088 Absolute and Gauge Pressure Transmitter
Rice Lake ITCM Weigh Modules
CAS CAST-X 2000 Circulation Heaters
Waltron 6051 Total Hardness Analyzer
Edgetech RH CAL Portable Relative Humidity Calibrator
CAS CAST-X 1000 Circulation Heaters
Megger Detex Phasing Tester
Jewell Instruments LSRP Series Inclinometer
Fluke 1625-2 GEO Earth Ground Tester
Honeywell FS20X Fire Sentry Detector
Pyxis SP-710 and SP-710B Water Multimeter